Filter Fan
FF 018 | 21m³/h to 102m³/h

  • Very low noise
  • Minimal depth in enclosure
  • Functional design
  • Time-saving installation
  • UV resistant

Filter fans are used to provide an optimum climate in enclosures. The interior temperature of an enclosure can be reduced by channelling cooler filtered outside air into the enclosure thus expelling heated internal air. The resulting air flow prevents formation of localised hot pockets and protects the electronic components from overheating. These filter fans are intended for indoor use. The plastic used for the hood is highly UV light resistant.

Axial fan, ball bearingservice life 50,000h at +25°C (+77°F), 65% RH
fan body aluminium, rotor plastic
Connection2 wires with pressure clamps 2.5mm², length 100mm
Casing (filter fan and exit filter)plastic according to UL94 V-0, light grey
Hood (filter fan and exit filter)plastic according to UL94 V-0, light grey;
UV light resistant according to UL746C (f1)
Mounting framewith double-sided industrial adhesive band for fixing to the
outside of enclosure; certain operating circumstances can
make the additional use of screws necessary (see drilling
template); a template for the enclosure cut-out is included
in the delivery of the filter fans
Filter matG4 acc. to DIN EN 779, filtering degree 94%
Filter materialsynthetic fibre with progressive construction, temperature
resistant to +100°C, self-extinguishing class F1,
moisture resistant to 100% RH, reusable - cleaning by
washing or vacuuming
Operating/Storage temperature-10 to +70°C (+14 to +158°F) / -40 to +70°C (-40 to +158°F)
Operating/Storage humiditymax. 90% RH (non-condensing)
Protection classI (earthed)
ApprovalsUL File No. E234324, EAC, VDE only: 230V

To top

Special features

  • The self-adhesive seal of the mounting frame prevents dust and water from entering the cabinet.
  • Functional design of the intake and exit fan hoods very effectively prevents direct intrusion of falling water and dust. The advantage is that the filter mat does not get so quickly contaminated with dirt and thus does not need to be exchanged so often.
  • The air channeling makes the filter fan particularly quiet in operation.
  • Functional and modern design enables time-saving assembly and maintenance.
  • The direction of air flow can easily be switched by reversing the axial fan (sizes 1 to 3).
  • EMC versions and other voltages on request.

To top

Filter Fan FF 018

Art. No.Operating voltageAir volume, free flowAir volume with exit filterCurrent con- sumptionPower con- sumptionAverage noise level (DIN EN ISO 4871)Depth in enclosureEnclosure cut-outWeight (approx.)Protection type
01800.0-00230VAC, 50Hz21m³/h16m³/h80mA13W31db (A)45mm97 x 97mm + 0.40.6kgIP54
01801.0-00230VAC, 50Hz55m³/h42m³/h100mA15W40db (A)58mm125 x 125mm + 0.41.0kgIP54/IP551
01802.0-00230VAC, 50Hz102m³/h68m³/h100mA15W39db (A)86mm176 x 176mm + 0.41.3kgIP54/IP551
01800.0-01120VAC, 60Hz24m³/h18m³/h160mA13W31db (A)45mm97 x 97mm + 0.40.6kgIP54
01801.0-01120VAC, 60Hz63m³/h48m³/h180mA15W40db (A)58mm125 x 125mm + 0.41.0kgIP54/IP551
01802.0-01120VAC, 60Hz117m³/h78m³/h180mA15W39db (A)86mm176 x 176mm + 0.41.3kgIP54/IP551

To top

1 Using fine filter mats type F5/M5 increases the protection type to IP55, but reduces the air volume

Time-saving assembly and maintenance

STEGO´s filter fans are easily installed by one person from outside the cabinet.

1.) Make cut-out in the cabinet wall. The cut edge of the cabinet opening should be free of dirt, filings and grease. A template for the enclosure cut-out is included in the delivery of the filter fan.
2.) Remove protective film from the sealing strips on the mounting frame. Press mounting frame into the cabinet opening. The frame stays permanently in the cabinet. (For size 176mm and up we recommend additional screw fixing.)
3.) Electrically connect the axial fan using the clip connectors. Push the unit into the mounting frame. Fix using screws.
4.) Insert the filter mat in the hood. Clip on. Finished.

Changing the filter mat or fan is quickly done by one person. To change the filter mat simply remove the filter hood, insert the new mat and snap the hood back again. No tools required. Maintenance of the fan can easily be done without removing the mounting frame (2).

To top

Exit Filter EF 118

Art. No.Depth in enclosureEnclosure cut-outWeight (approx.)Filter matProtection type
11800.0-0016mm97 x 97mm + 0.40.3kgG4 acc. to DIN EN 779, filtering degree 94%IP54
11801.0-0016mm125 x 125mm + 0.40.4kgG4 acc. to DIN EN 779, filtering degree 94%IP54/IP551
11802.0-0016mm176 x 176mm + 0.40.6kgG4 acc. to DIN EN 779, filtering degree 94%IP54/IP551

To top

1 Using fine filter mats type F5/M5 increases the protection type to IP55, but reduces the air volume

Filter Mat FM 086/FFM 086

Filter mat89 x 89mm118 x 118mm168 x 168mm
G4 (1 packaging unit = 3 pcs.)Art. No. 08600.0-00Art. No. 08601.0-00Art. No. 08602.0-00
F5/M5 (1 packaging unit = 3 pcs.)     -Art. No. 08604.0-00Art. No. 08605.0-00

To top

Technical Drawings

Filter Fan FF 018

To top